Fri Feb 11 07:27:51 CST 2005
The Btuh Gain for 15 SqFt of North and Shaded Double Pane Glass =
300
There is no calculation for NorthEast and NorthWest Glass
The
Btuh Gain for 960 SqFt of East and West Double Pane Glass = 91200
The Btuh Gain for 120 SqFt of SouthEast and SouthWest Double Pane
Glass = 12000
The Btuh Gain for 240 SqFt of South Double Pane
Glass = 16800
There is no calculation for SkyLights
There is no
calculation for Windows in Doors
The Btuh Gain for 408 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 1060.8
The Btuh Gain for 0 SqFt of Wood No Insulation 1/2"
Gypsum Wall Number 2 = 0
The Btuh Gain for 312 SqFt of Wood
R-11 & 1/2" Gypsum Wall Number 3 = 811.2
The Btuh Gain for 264
SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 686.4
The Btuh Gain for 1078 SqFt of Roof Only 3" - 3.5" R-11; Ceiling
Number 1 = 8839.6
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 31 People = 310
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1078 SqFt of Area Lighting in an Office = 3234
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 1442.7
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 178523
The Total Tons of HVAC needed = 14.8769166666667