HVAC ProjectProject Faith Bible Church/Offices HVAC Calculations Mon Feb 14 15:07:23 CST 2005 The Btuh Gain for 15 SqFt of North and Shaded Double Pane Glass = 300 There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 15 SqFt of East and West Double Pane Glass = 1425 The Btuh Gain for 30 SqFt of SouthEast and SouthWest Double Pane Glass = 3000 There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 31 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 80.6 The Btuh Gain for 380 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 2 = 988 The Btuh Gain for 770 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 3 = 2002 There is no calculation for Wall Number 4 The Btuh Gain for 1686 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 8767.2 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 84 People = 840 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 1686 SqFt of Area Lighting in an Office = 5058 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Office Space Outside Fresh Air #4 = 1680 cfm The Btuh Gain for Outside Fresh Air #4 = 50400 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 1680 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 72860.8 The Total Tons of HVAC needed = 6.07173333333333