Tue Aug 23 10:16:51 CDT 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
The Btuh Gain for 40 SqFt of South Single Pane Glass = 3200
There is no calculation for SkyLights
There is no calculation for
Windows in Doors
The Btuh Gain for 1380 SqFt of Mason Above Grade R-11 Wall Number 1 =
2208
The Btuh Gain for 1380 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 2 = 3588
The Btuh Gain for 1380 SqFt of
Wood R-11 & 1/2" Gypsum Wall Number 3 = 3588
The Btuh Gain for
1380 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 3588
The Btuh Gain for 3600 SqFt of Roof Only 2" - 2.5" R-7; Ceiling Number
1 = 39600
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 240 People = 2400
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 3600 SqFt of Area Lighting in a Retail Store = 14400
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 3600
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 180572
The Total Tons of HVAC needed = 15.0476666666667