Tue Aug 23 11:38:42 CDT 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
The Btuh Gain for 60
SqFt of East and West Single Pane Glass = 6600
There is no
calculation for SouthEast and SouthWest Glass
There is no calculation for
South Glass
There is no calculation for SkyLights
There is no
calculation for Windows in Doors
The Btuh Gain for 920 SqFt of Mason Above Grade R-11 Wall Number 1 =
1472
The Btuh Gain for 1380 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 2 = 3588
The Btuh Gain for 920 SqFt of Wood
R-11 & 1/2" Gypsum Wall Number 3 = 2392
The Btuh Gain for 1380
SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 3588
The Btuh Gain for 2400 SqFt of Roof Only 6" - 7" R-22; Ceiling Number
1 = 11520
The Btuh Gain for 2400 SqFt of Roof Only 6" - 7"
R-22; Ceiling Number 2 = 11520
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 290 People = 2900
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 4800 SqFt of Area Lighting in an Office = 14400
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 5800
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 231980
The Total Tons of HVAC needed = 19.3316666666667