Project Zone 3 - Childrens Worship & Classrooms HVAC Calculations

Mon Oct 6 16:33:45 EDT 2008

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 1100 SqFt of Mason Above Grade No Insulation Wall Number 1 = 11990
The Btuh Gain for 550 SqFt of Mason Above Grade No Insulation Wall Number 2 = 5995
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 4933 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 40450.6

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 284 People = 2840

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 4933 SqFt of Area Lighting in a Retail Store = 19732

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Reception Area Outside Fresh Air #4 = 3750 cfm
The Btuh Gain for Outside Fresh Air #4 = 112500
The Reception Area Outside Fresh Air #5 = 510 cfm
The Btuh Gain for Outside Fresh Air #5 = 15300
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 4260
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 208807.6

The Total Tons of HVAC needed = 17.4006333333333