Mon Oct 6 17:01:48 EDT 2008
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
The Btuh Gain for 540
SqFt of East and West Single Pane Glass = 59400
There is no
calculation for SouthEast and SouthWest Glass
There is no calculation for
South Glass
There is no calculation for SkyLights
There is no
calculation for Windows in Doors
The Btuh Gain for 1397 SqFt of Mason Above Grade No Insulation Wall
Number 1 = 15227.3
The Btuh Gain for 671 SqFt of Mason Above
Grade No Insulation Wall Number 2 = 7313.9
There is no calculation
for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 7757 SqFt of Roof Only 3" - 3.5" R-11; Ceiling
Number 1 = 63607.4
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 437 People = 4370
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 7757 SqFt of Area Lighting in an Office = 23271
The wattage for 15 Gallon Coffee Machines = 7050
There is
no calculation for Electric Food Warmers
There is no calculation for Gas
Food Warmers
There is no calculation for Electric Fry Kettle
There is no
calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair
Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no
calculation for other appliances of known wattages
The Total Outside Fresh Air CFM = 7755
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 429809.6
The Total Tons of HVAC needed = 35.8174666666667