SECTION
07570
SWD Urethane
Company
COATED FOAM ROOFING
SYSTEM
Part 1 GENERAL
SUMMARY
Section Includes: Coated foam roofing, as shown on
drawings and specified herein.
1.01
SYSTEM
DESCRIPTION:
a.
One inch (minimum) of
sprayed Polyurethane Foam (additional inches may be added and /or sloped
depending upon desired insulation value) on the deck surface with 25 mil
thickness of white, reflective 100% acrylic roof coating with #9 white limestone
granules or #11 ceramic granules imbedded into or on top of the wet coating at
(50) pounds per 100 square feet. The roof system will provide a 10-year, no-leak
warranty.
b.
Low cost sustainable
foam roof system is easily maintained, repaired and upon inspection, may be
re-coated with elastomeric protective coating after 10
years.
1.02
SUBMTTTALS
1.03
QUALITY
ASSURANCE
1.04
DELIVERY, STORAGE AND
HANDLING
1.05
PROJECT/SITE
CONDITIONS
1.06
WARRANTY
Part 2. PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
a.
Property
Procedure
Values
Density, pcf nominal *
D- 1622
2.5 - 3.0
Compressive, psi
D-1621
50
Tensile, psi
D-1623
85
Shear, psi
D-273
50
Closed Cell Content %
D-2865
95
Permeance, per/inch
E-96
2-3
R Value
C- 177
6.8
k-Factor (initial)
C- 177
0.148
a. Polyurethane Foam
Density and Compressive Strength shall be uniform and consistent with
specification. Minimum Physical Properties shall not allow for multiple foam
densities or compressive strengths to be applied within multiple inches of
specified foam.
b. Polyurethane Foam shall
contain EPA-approved 245fa blowing agent and meet U.S. non-ozone depleting
requirements of the U.S. EPA mandate blowing agent is acceptable.
c. SWD Urethane Company,
SWD 125 “Quik-Shield”® Polyurethane Foam with HFC 245fa blowing agent is
acceptable
a. SWD 1929F “Kool-Kote”™
100% acrylic elastomeric UL 723 Class I Rated white coating meets EPA "Energy
Star" and CRRC guidelines for Solar Reflectance and Thermal Emittance and can be
applied by brush, roller or conventional airless spray equipment with the
following Minimum Physical
Properties:
b. Property
Procedure
Values
Solids Content
By Weight
ASTM D-1353
70%
By Volume
ASTM D-2697
60%
Solar Reflectance
ASTM E-903
83%
Thermal Emittance
ASTM E-408
95 %
Ultimate Tensile Strength:
Psi
ASTM D-412
280
Elongation at Break:
Psi
ASTM D-412
355
Permeance
Perms @ 20
mils
ASTM E-96
3.5
Hardness:
Shore A
Durometer
ASTM D-2240
60
All Tests Required
ASTM D-6083
pass
Colors:
Grey, Buff, White
Note: SWD Urethane Company is an original "Energy
Star" partner and approved by CRRC.
c. Dry film thickness
shall be 25 mils application with #9 limestone granules or #11 ceramic granules
embedded at 50 Ibs per 100 square feet.
d. Base coat and top coat
should be contrasting colors to ensure adequate thickness and
coverage.
e. SWD Urethane Company
"Kool-Kote"™ 1929F Acrylic Elastomeric Coatings are
acceptable.
Note: This
material complies with all the requirements of ASTM D-6083 standard
specification for liquid applied acrylic coating used in
roofing.
Part 3. EXECUTION
3.01 EXAMINATION
3.02 PREPARATION
a.
All loose gravel, dust
and residue shall be removed using power-vacuum equipment, power-sweeper,
air-blowing or other suitable means. (Special conditions may be required if
asbestos products are a part of roof removal.)
b.
The existing roof shall
be thoroughly inspected for adhesion between felts, insulation and deck. Areas
of poor adhesion should be fastened. Blisters, buckles, wrinkles and fish-mouths
shall be cut out and/or fastened.
c.
Remove or re-fasten all
loose base flashing, counter-flashing and gravel-stops, as
required.
a.
The metal roof deck
shall be constructed of minimum 22-gauge steel. Construction shall conform to
local building codes.
b.
Ferrous Metal:
Sandblast iron and steel surfaces, which are not primed, shoppainted, or
otherwise protected- Remove loose rust and primer from shop-primed iron and
steel surfaces by scraping or wire brushing.
c.
Non-Ferrous Metal :
Clean galvanized metal, aluminum and stainless steel surfaces, as recommended by
the manufacturer issuing the warranty.
d.
If the metal surface is
free of loose scale, rust, weathered or chalking paint, it can be cleaned using
compressed air-jet, vacuum equipment, hand or powerbroom to remove loose dirt.
Grease, oil or other contaminants shall be removed with proper cleaning
solutions.
e.
Fluted metal decks
require a suitable method of covering or filling the flute prior to polyurethane
foam application. Flutes may be covered with a suitable board stock, special
polyester tape, pro-cut board stock or spray-applied polyurethane foam. Where a
fire barrier is required, apply Type X gypsum board, mechanically-fastened to
the metal surface, to meet local building code
requirements.
f.
Metal flutes up to
three (3) inches in width, may be taped with 4" clear adhesive tape then sprayed
with a minimum of ½” of foam.
a.
Remove loose dirt, dust
and debris by using compressed air, vacuum equipment or a broom. Oil and grease
from release agents or other contaminants shall be removed with proper cleaning
solutions.
b.
All joint openings in
concrete decks that exceed ¼” shall be grouted or caulked by others, prior to
application of polyurethane foam.
c.
Priming is required on
concrete surfaces and it is recommended that due to hydration that is present,
poured concrete decks be permitted to cure for twenty-eight (28) days prior to
the application of sprayed polyurethane foam.
d.
Sprayed polyurethane
foam is not recommended for application to lightweight or insulating concrete
materials unless underlayment and/or vent pans are installed. (Check with
manufacturer prior to installation of PUF roof system over lightweight
concrete).
a.
Deck must meet building
code requirements for resistance to wind uplift.
b.
Plywood shall contain
no more than 18% water, as measured in accordance with ASTM Standards. Plywood
shall be exterior grade not less than 1/2" thick, nailed firmly in
place.
c.
Plywood joints in
excess of ¼”, shall be taped or filled by others with a suitable sealant
material, prior to application of polyurethane foam.
d.
Deck shall be free of
loose dirt, grease, oil or other contaminants prior to priming or foam
application. Remove loose dirt or debris by use of compressed air, vacuum or
broom. No washing shall be permitted.
e.
Tongue & Groove
Sheathing or Planking: Due to the frequency of joints, possibility of variable openings and
effects of aging and shrinking, these surfaces must be overlaid with a minimum
of ½” thick exterior grade plywood or other suitable covering with a minimum 1"
foam thickness.
a.
Such materials used
over fluted metal decks must be installed with mechanical fasteners or
adhesives.
b.
Fasteners shall be
installed to meet Factory Mutual wind uplift criteria or the appropriate local
building code criteria.
c.
Boards shall be firmly
butted together along edges without gaps or openings. Joints exceeding ¼” shall
be caulked by others with a suitable sealant material.
d.
Care shall be taken to
prevent mineral or gypsum board from getting wet in storage on the job-site and
after installation, prior to being protected by foam. Moisture exposure may
damage these materials and require replacement.
e.
Remove loose dirt and
debris by using compressed air, vacuum or broom. No power-broom is permitted due
to possibility of damage. The installed materials shall be protected from spills
of contaminants
3.03 INSTALLATION - GENERAL
a.
Using ½” CDX plywood
and structural lumber adhered mechanical1y to the substrate and vertical walls
installed by others.
b.
Using spray
polyurethane foam (within certain sloping requirements).
c.
Using tapered
insulation board which shall be secured to the substrate with an adhesive
recommended by the tapered board manufacturer or with mechanical -
fasteners.
3.O4 INSTALLATION –
PRIMER/SEALER
3.05 INSTALLATION - POLYURETHANE
FOAM
3.06 INSTALLATION - PROTECTIVE ELASTOMERIC
COATING
B.
Base
Coat:
3.07 CLEANING