Kenner Regional Pre-Op Holding HVAC ProjectProject Kenner Regional Pre-Op Holding HVAC Calculations Tue Jun 28 08:50:39 CDT 2005 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass There is no calculation for East and West Glass There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 360 SqFt of Mason Above Grade No Insulation Wall Number 1 = 3924 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 There is no calculation for Ceiling Number 1 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 15 People = 150 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 987 SqFt of Area Lighting in an Office = 2961 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster 7800 watts are being calculated for BTUh There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Reception Area Outside Fresh Air #4 = 225 cfm The Btuh Gain for Outside Fresh Air #4 = 6750 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 225 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 40305 The Total Tons of HVAC needed = 3.35875