Project Shoney's - Comfort Inn HVAC Calculations

Fri Aug 26 15:00:45 CDT 2005

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 90 SqFt of East and West Single Pane Glass = 9900
There is no calculation for SouthEast and SouthWest Glass
The Btuh Gain for 26 SqFt of South Single Pane Glass = 2080
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 360 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 936
The Btuh Gain for 480 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 2 = 1248
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 707 SqFt of Ceiling and Roof Combo No Insulation; Ceiling Number 1 = 19796
The Btuh Gain for 821 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 2 = 19796

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 8 People = 80

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1528 SqFt of Area Lighting in an Office = 4584

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Reception Area Outside Fresh Air #1 = 630 cfm
The Btuh Gain for Outside Fresh Air #1 = 18900
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 630
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 61793.2

The Total Tons of HVAC needed = 5.14943333333333