Project Best Building Supply Showroom HVAC HVAC Calculations

Wed May 24 12:51:13 CDT 2006

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of East and West Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 569 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 1 = 1308.7
The Btuh Gain for 625 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 2 = 1437.5
The Btuh Gain for 867 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 3 = 1994.1
The Btuh Gain for 795 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 1351.5

The Btuh Gain for 4591 SqFt of Roof Only No Insulation; Ceiling Number 1 = 197413

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 8 People = 80

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 4590 SqFt of Area Lighting in a Retail Store = 18360

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Reception Area Outside Fresh Air #1 = 4131 cfm
The Btuh Gain for Outside Fresh Air #1 = 123930
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 4131
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 345874.8

The Total Tons of HVAC needed = 28.8229