Thu Dec 22 13:55:05 CST 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
There is no calculation for South Glass
There is no calculation
for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 513 SqFt of Wood R-19 & 1/2" Gypsum Wall Number
1 = 872.1
The Btuh Gain for 959 SqFt of Wood R-19 & 1/2"
Gypsum Wall Number 2 = 1630.3
The Btuh Gain for 348 SqFt of
Wood R-19 & 1/2" Gypsum Wall Number 3 = 591.6
The Btuh Gain for
794 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 1349.8
The Btuh Gain for 2160.64 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 10371.072
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
There is no calculation for People
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2160.64 SqFt of Area Lighting in a Retail Store = 8642.56
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
The wattage for 15 SqFt of Gas Food Warmers =
1800
There is no calculation for Electric Fry Kettle
The wattage
for 12 SqFt of Gas Fry Kettle = 24000
There is no calculation
for Electric Griddle
The wattage for 60 SqFt of Gas Griddle =
120000
There is no calculation for Hair Dryer Helmets
There is no
calculation for 4-Slice Toaster
There is no calculation for other appliances
of known wattages
The Total Outside Fresh Air CFM = 3024.896
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 609924.312
The Total Tons of HVAC needed = 50.827026