Tue Jun 29 12:01:14 EDT 2010
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
The Btuh Gain for 152 SqFt of SouthEast and
SouthWest Single Pane Glass = 16720
There is no calculation for South
Glass
There is no calculation for SkyLights
The Btuh Gain for 20
SqFt of Windows in Doors = 264
The Btuh Gain for 152 SqFt of Mason Above Grade R-5 Wall Number 1 =
471.2
The Btuh Gain for 1235 SqFt of Wood R-13 & 1/2"
Gypsum Wall Number 2 = 2840.5
The Btuh Gain for 1235 SqFt of
Wood R-13 & 1/2" Gypsum Wall Number 3 = 2840.5
The Btuh Gain for
152 SqFt of Mason Above Grade No Insulation Wall Number 4 = 1656.8
The Btuh Gain for 1268 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 6593.6
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 12 People = 120
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1268 SqFt of Area Lighting in an Office = 3804
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 820.4
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 59922.6
The Total Tons of HVAC needed = 4.99355