Project NORTHSHORE DAIQUIRIS TO-GO HVAC Calculations

Mon May 16 10:04:36 CDT 2005

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 106 SqFt of East and West Double Pane Glass = 10070
There is no calculation for SouthEast and SouthWest Glass
The Btuh Gain for 89 SqFt of South Double Pane Glass = 6230
There is no calculation for SkyLights
The Btuh Gain for 40 SqFt of Windows in Doors = 528

There is no calculation for Wall Number 1
There is no calculation for Wall Number 2
The Btuh Gain for 156 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 3 = 405.6
The Btuh Gain for 130 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 338

The Btuh Gain for 615 SqFt of Roof Only 8" - 9.5" R-30; Ceiling Number 1 = 1968

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 13 People = 130

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 615 SqFt of Area Lighting in a Retail Store = 2460

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
8438 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Dining Room Outside Fresh Air #4 = 240 cfm
The Btuh Gain for Outside Fresh Air #4 = 7200
The Kitchen Outside Fresh Air #5 = 15 cfm
The Btuh Gain for Outside Fresh Air #5 = 450
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 255
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 58468.8

The Total Tons of HVAC needed = 4.8724