Mon May 16 10:04:36 CDT 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
The Btuh Gain for 106
SqFt of East and West Double Pane Glass = 10070
There is no
calculation for SouthEast and SouthWest Glass
The Btuh Gain for 89
SqFt of South Double Pane Glass = 6230
There is no calculation
for SkyLights
The Btuh Gain for 40 SqFt of Windows in Doors = 528
There is no calculation for Wall Number 1
There is no calculation for
Wall Number 2
The Btuh Gain for 156 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 3 = 405.6
The Btuh Gain for 130 SqFt of
Wood R-11 & 1/2" Gypsum Wall Number 4 = 338
The Btuh Gain for 615 SqFt of Roof Only 8" - 9.5" R-30; Ceiling Number
1 = 1968
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 13 People = 130
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 615 SqFt of Area Lighting in a Retail Store = 2460
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
8438 watts are being
calculated for BTUh
The Total Outside Fresh Air CFM = 255
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 58468.8
The Total Tons of HVAC needed = 4.8724