Tue May 24 14:15:15 CDT 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 84.00 SqFt of NorthEast and NorthWest Double
Pane Glass = 5880
The Btuh Gain for 0 SqFt of East and West
Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SouthEast
and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt
of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of
SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors =
0
The Btuh Gain for 276.00 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 469.2
The Btuh Gain for 620.04 SqFt of Mason Above
Grade R-11 Wall Number 2 = 992.064
The Btuh Gain for 0 SqFt of
Mason Above Grade No Insulation Wall Number 3 = 0
The Btuh Gain for
0 SqFt of Mason Above Grade No Insulation Wall Number 4 = 0
The Btuh Gain for 2503.75 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 12018
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 18 People = 180
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2503.75 SqFt of Area Lighting in an Office = 7511.25
The wattage for 0 Gallon Coffee Machines = 0
The wattage
for 0 SqFt of Electric Food Warmers = 0
The wattage for 0
SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of
Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry
Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage
for 0 Hair Dryer Helmets = 0
The wattage for 2503.75
4-Slice Toasters = 0
0 watts are being calculated for
BTUh
The Total Outside Fresh Air CFM = 360
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 37850.514
The Total Tons of HVAC needed = 3.1542095