Project STARLIGHT BAPTIST UNIT 8 HVAC Calculations

Tue May 24 14:36:04 CDT 2005

The Btuh Gain for 60.64 SqFt of North and Shaded Double Pane Glass = 1212.8
The Btuh Gain for 154.00 SqFt of NorthEast and NorthWest Double Pane Glass = 10780
The Btuh Gain for 297.50 SqFt of East and West Double Pane Glass = 28262.5
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 534.75 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 909.075
The Btuh Gain for 637.33 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 2 = 1083.461
The Btuh Gain for 377.58 SqFt of Wood No Insulation 1/2" Gypsum Wall Number 3 = 2945.124
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 4 = 0

The Btuh Gain for 1328.86 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 6378.528

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 9 People = 90

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1328.86 SqFt of Area Lighting in an Office = 3986.58

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 1328.86 4-Slice Toasters = 0
0 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Office Space Outside Fresh Air #4 = 180 cfm
The Btuh Gain for Outside Fresh Air #4 = 5400
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 180
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 61048.068

The Total Tons of HVAC needed = 5.087339