Project STARLIGHT BAPTIST UNIT 9 HVAC Calculations

Wed May 25 12:29:41 CDT 2005

The Btuh Gain for 43.33 SqFt of North and Shaded Double Pane Glass = 866.6
The Btuh Gain for 128.33 SqFt of NorthEast and NorthWest Double Pane Glass = 8983.1
The Btuh Gain for 290.00 SqFt of East and West Double Pane Glass = 27550
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 5.00 SqFt of Windows in Doors = 66

The Btuh Gain for 292.54 SqFt of Mason Above Grade R-11 Wall Number 1 = 468.064
The Btuh Gain for 252.87 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 2 = 429.879
The Btuh Gain for 585.375 SqFt of Mason Above Grade R-11 Wall Number 3 = 936.6
There is no calculation for Wall Number 4

The Btuh Gain for 2093.31 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 10885.212

There is no calculation for Ceiling Number 2

The Btuh Gain for 0 SqFt of Over Basement Floor Number 1 = 0
The Btuh Gain for 0 SqFt of Over Basement Floor Number 2 = 0

The Btuh Gain for 15 People = 150

The Btuh Gain for Motor 0 HP = 0

The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0

The Btuh Gain for 2093.31 SqFt of Area Lighting in an Office = 6279.93

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 2093.31 4-Slice Toasters = 0
0 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Office Space Outside Fresh Air #4 = 300 cfm
The Btuh Gain for Outside Fresh Air #4 = 9000
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 300
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 65615.385

The Total Tons of HVAC needed = 5.46794875