HVAC ProjectProject Faith Bible Church Assembly HVAC Calculations Tue Feb 15 07:00:10 CST 2005 The Btuh Gain for 96 SqFt of North and Shaded Single Pane Glass = 2880 The Btuh Gain for 100 SqFt of NorthEast and NorthWest Triple Pane Glass = 5600 There is no calculation for East and West Glass There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 380 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 988 The Btuh Gain for 200 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 2 = 520 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 1488 SqFt of Roof Only 10" - 12" R-38; Ceiling Number 1 = 3868.8 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 92 People = 920 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 1488 SqFt of Area Lighting in a Retail Store = 5952 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Reception Area Outside Fresh Air #4 = 1380 cfm The Btuh Gain for Outside Fresh Air #4 = 41400 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 1380 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 62128.8 The Total Tons of HVAC needed = 5.1774