Project Christian Life Assembly of God HVAC Calculations

Thu Apr 28 12:52:12 CST 2005

The Btuh Gain for 90 SqFt of North and Shaded Single Pane Glass = 2700
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
The Btuh Gain for 54 SqFt of South Single Pane Glass = 4320
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 1200 SqFt of Mason Above Grade R-11 Wall Number 1 = 1920
The Btuh Gain for 1200 SqFt of Mason Above Grade R-11 Wall Number 2 = 1920
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 5485 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 28522

The Btuh Gain for 1250 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 2 = 28522

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 500 People = 5000

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 6735 SqFt of Area Lighting in an Office = 20205

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Reception Area Outside Fresh Air #4 = 7500 cfm
The Btuh Gain for Outside Fresh Air #4 = 225000
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 7500
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 296087

The Total Tons of HVAC needed = 24.6739166666667