Project La Quinta Hwy 21 HVAC Calculations

Mon Feb 28 08:37:39 CST 2005

The Btuh Gain for 195 SqFt of North and Shaded Double Pane Glass = 3900
The Btuh Gain for 50 SqFt of NorthEast and NorthWest Double Pane Glass = 3500
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for SkyLights
The Btuh Gain for 60 SqFt of Windows in Doors = 792

The Btuh Gain for 122 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 317.2
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 4580 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 37556

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 76 People = 760

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 4580 SqFt of Area Lighting in an Office = 13740

The wattage for 3 Gallon Coffee Machines = 1410
The wattage for 20 SqFt of Electric Food Warmers = 2400
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
The wattage for 4580 4-Slice Toasters = 2460
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Reception Area Outside Fresh Air #4 = 1140 cfm
The Btuh Gain for Outside Fresh Air #4 = 34200
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 1140
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 116083.2

The Total Tons of HVAC needed = 9.6736