Tue May 17 12:25:12 CDT 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane
Glass = 0
The Btuh Gain for 50.00 SqFt of East and West Single
Pane Glass = 5500
The Btuh Gain for 0 SqFt of SouthEast and
SouthWest Single Pane Glass = 0
The Btuh Gain for 63.332 SqFt
of South Single Pane Glass = 5066.56
The Btuh Gain for 0 SqFt
of SkyLights = 0
The Btuh Gain for 64.00 SqFt of Windows in
Doors = 844.8
The Btuh Gain for 747.50 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 1270.75
The Btuh Gain for 433.25 SqFt of Wood R-19
& 1/2" Gypsum Wall Number 2 = 736.525
The Btuh Gain for 530.75
SqFt of Wood R-19 & 1/2" Gypsum Wall Number 3 = 902.275
The
Btuh Gain for 650.00 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 =
1105
The Btuh Gain for 2248.00 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 11689.6
The Btuh Gain for 0 SqFt of Roof Only No Insulation; Ceiling Number 2 = 11689.6The Btuh Gain for 0 SqFt of Above Grade R-11 Floor Number 1 = 0
The Btuh Gain for 0 SqFt of Over Basement Floor Number 2 = 0
The Btuh Gain for 5 People = 50
The Btuh Gain for Motor 0 HP = 0
The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0
The Btuh Gain for 2248.00 SqFt of Area Lighting in an Office = 6744
The wattage for 0 Gallon Coffee Machines = 0
The wattage
for 0 SqFt of Electric Food Warmers = 0
The wattage for 0
SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of
Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry
Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage
for 0 Hair Dryer Helmets = 0
The wattage for 2248.00
4-Slice Toasters = 0
0 watts are being calculated for
BTUh
The Total Outside Fresh Air CFM = 314.72
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 43351.11
The Total Tons of HVAC needed = 3.6125925