Thu Dec 22 13:47:08 CST 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
There is no calculation for NorthEast and NorthWest Glass
The Btuh
Gain for 746.16 SqFt of East and West Double Pane Glass = 70885.2
There is no calculation for SouthEast and SouthWest Glass
The Btuh
Gain for 380 SqFt of South Double Pane Glass = 26600
The Btuh
Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 63
SqFt of Windows in Doors = 831.6
The Btuh Gain for 603.76 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 1026.392
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for
Wall Number 4
The Btuh Gain for 2537.14 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 12178.272
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
There is no calculation for People
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2537.14 SqFt of Area Lighting in a Retail Store = 10148.56
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 3551.996
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 228229.904
The Total Tons of HVAC needed = 19.0191586666667