Project South Seas Chinese Dining Area HVAC HVAC Calculations

Thu Dec 22 13:47:08 CST 2005

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 746.16 SqFt of East and West Double Pane Glass = 70885.2
There is no calculation for SouthEast and SouthWest Glass
The Btuh Gain for 380 SqFt of South Double Pane Glass = 26600
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 63 SqFt of Windows in Doors = 831.6

The Btuh Gain for 603.76 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 1026.392
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 2537.14 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 12178.272

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

There is no calculation for People

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 2537.14 SqFt of Area Lighting in a Retail Store = 10148.56

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Dining Room Outside Fresh Air #1 = 3551.996 cfm
The Btuh Gain for Outside Fresh Air #1 = 106559.88
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 3551.996
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 228229.904

The Total Tons of HVAC needed = 19.0191586666667