Mon Jun 12 13:23:00 CDT 2006
There is no calculation for North & Shaded Glass
The Btuh Gain for
372 SqFt of NorthEast and NorthWest Single Pane Glass = 33480
The Btuh Gain for 576 SqFt of East and West Single Pane Glass =
63360
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for
SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 552 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 1435.2
There is no calculation for Wall Number 2
There is no
calculation for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 1635 SqFt of Roof Only 2" - 2.5" R-7; Ceiling Number
1 = 17985
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 56 People = 560
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
There is no calculation for Lighting
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 1090
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 149520.2
The Total Tons of HVAC needed = 12.4600166666667