Project Quiznos 10006 HVAC Calculations

Wed Aug 9 06:29:37 CDT 2006

There is no calculation for North & Shaded Glass
The Btuh Gain for 520 SqFt of NorthEast and NorthWest Single Pane Glass = 46800
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 1358 SqFt of Mason Above Grade No Insulation Wall Number 1 = 14802.2
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 1144 SqFt of Roof Only 2" - 2.5" R-7; Ceiling Number 1 = 12584

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 17 People = 170

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1144 SqFt of Area Lighting in a Retail Store = 4576

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Cafeteria or Fast Food Outside Fresh Air #4 = 240 cfm
The Btuh Gain for Outside Fresh Air #4 = 7200
The Kitchen Outside Fresh Air #5 = 75 cfm
The Btuh Gain for Outside Fresh Air #5 = 2250
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 315
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 88382.2

The Total Tons of HVAC needed = 7.36518333333333