Thu Jan 19 12:55:25 CST 2006
There is no calculation for North & Shaded Glass
The Btuh Gain for
130 SqFt of NorthEast and NorthWest Single Pane Glass = 11700
There is no calculation for East and West Glass
There is no
calculation for SouthEast and SouthWest Glass
There is no calculation for
South Glass
There is no calculation for SkyLights
The Btuh Gain for
30 SqFt of Windows in Doors = 396
The Btuh Gain for 200 SqFt of Wood No Insulation 1/2" Gypsum Wall
Number 1 = 1560
There is no calculation for Wall Number 2
There
is no calculation for Wall Number 3
There is no calculation for Wall Number
4
The Btuh Gain for 1780 SqFt of Roof Only No Insulation; Ceiling Number
1 = 76540
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 28 People = 280
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1780 SqFt of Area Lighting in a Retail Store = 7120
The wattage for 10 Gallon Coffee Machines = 4700
There is
no calculation for Electric Food Warmers
There is no calculation for Gas
Food Warmers
There is no calculation for Electric Fry Kettle
There is no
calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair
Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no
calculation for other appliances of known wattages
The Total Outside Fresh Air CFM = 520
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 129176
The Total Tons of HVAC needed = 10.7646666666667