Office, Kitchen, Center ClassRooms Rainbow Child Care HVAC ProjectProject Office, Kitchen, Center ClassRooms Rainbow Child Care HVAC Calculations Fri Sep 19 11:12:16 EDT 2008 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 60 SqFt of East and West Single Pane Glass = 6600 There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights The Btuh Gain for 40 SqFt of Windows in Doors = 528 The Btuh Gain for 480 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 1248 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 2936 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 24075.2 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 There is no calculation for People There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 2936 SqFt of Area Lighting in a Retail Store = 11744 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Office Space Outside Fresh Air #4 = 400 cfm The Btuh Gain for Outside Fresh Air #4 = 12000 The Dining Room Outside Fresh Air #5 = 400 cfm The Btuh Gain for Outside Fresh Air #5 = 12000 The Office Space Outside Fresh Air #6 = 240 cfm The Btuh Gain for Outside Fresh Air #6 = 7200 The Total Outside Fresh Air CFM = 1040 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 75395.2 The Total Tons of HVAC needed = 6.28293333333333