IMC 2021 Tbl 403.3.1.1 Large ClassRoom; age 9 + Vbz = RpPz + Ra Az Rp = 10 Pz = 35 per 1000 ft2 = 13.4 people Ra = 0.12 Az = 404.0 ft2 - 5 % for furniture = 383.80 ft2 Vbz = 180.39 cfm fresh air per classroom ************************************************************ Small Classrooms; age 9 + Vbz = RpPz + Ra Az Rp = 10 Pz = 35 per 1000 ft2 = 10.0 people Ra = 0.12 Az = 300.00 ft2 - 5 % = 285.00 ft2 Vbz = 134.0 cfm fresh air per small classroom ************************************************************ Down Stair Office Vbz = RpPz + Ra Az Rp = 5 Pz = 5 per 1000 ft2 = 0.6 people Ra = 0.06 Az = 133.00 ft2 - 5 % = 126.35 ft2 Vbz = 10.7 cfm fresh air per small classroom ************************************************************ Up Stair Offices Vbz = RpPz + Ra Az Rp = 0 Pz = 0 per 1000 ft2 = 0.0 people Ra = 0.06 Az = 704.00 ft2 - 5 % = 668.80 ft2 Vbz = 40.1 cfm fresh air per small classroom ************************************************************ ************************************************************ Down Stair Corridors Vbz = RpPz + Ra Az Rp = 5 Pz = 5 per 1000 ft2 = 3.9 people Ra = 0.06 Az = 813.00 ft2 - 5 % = 772.35 ft2 Vbz = 65.6 cfm fresh air per small classroom ************************************************************ Infiltration Manual N Table 13b Number of Students per day per wing = 107.5 Number of Times Students open door per day = 4.0 times Length of Stay = 3.0 hr Traffic Rate = 72 /hr Number of Employees = 8 Number of Times Employees open door per day = 4.0 times Length of Stay = 3 HR Traffic Rate = 5 /hr Total Traffic Rate = 77 /hr cfm Infiltration per door based on traffic rate : Winter Summer Double door no vestibule has an infiltration rate of 779 448 Total Door Infiltration in cfm 779 448 Therefore each corridor with 8 classrooms will get 412 cfm of fresh air during the day. Each classroom that receives 170 cfm of fresh air from ERV the additional 4 cfm fresh air will come from the corridor. Each classroom that receives 140 cfm fresh air from ERV the additional 34 cfm will enter the classroom from the corridor. Required cfm per wing = 180.4 cfm x 8 classrooms 1443 cfm in addition each corridor requires #REF! cfm Totals #REF! cfm Each wing has an ERV supplying 1300 cfm Each wing has door infiltration 448 cfm Total fresh air "1,748" cfm > #REF! cfm