Wed May 25 12:29:41 CDT 2005
The Btuh Gain for 43.33 SqFt of North and Shaded Double Pane Glass =
866.6
The Btuh Gain for 128.33 SqFt of NorthEast and NorthWest
Double Pane Glass = 8983.1
The Btuh Gain for 290.00 SqFt of
East and West Double Pane Glass = 27550
The Btuh Gain for 0
SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh
Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain
for 0 SqFt of SkyLights = 0
The Btuh Gain for 5.00 SqFt
of Windows in Doors = 66
The Btuh Gain for 292.54 SqFt of Mason Above Grade R-11 Wall Number 1
= 468.064
The Btuh Gain for 252.87 SqFt of Wood R-19 &
1/2" Gypsum Wall Number 2 = 429.879
The Btuh Gain for 585.375
SqFt of Mason Above Grade R-11 Wall Number 3 = 936.6
There is no
calculation for Wall Number 4
The Btuh Gain for 2093.31 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 10885.212
There is no calculation for Ceiling Number 2
The Btuh Gain for 0 SqFt of Over Basement Floor Number 1 = 0
The Btuh Gain for 0 SqFt of Over Basement Floor Number 2 = 0
The Btuh Gain for 15 People = 150
The Btuh Gain for Motor 0 HP = 0
The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0
The Btuh Gain for 2093.31 SqFt of Area Lighting in an Office = 6279.93
The wattage for 0 Gallon Coffee Machines = 0
The wattage
for 0 SqFt of Electric Food Warmers = 0
The wattage for 0
SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of
Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry
Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage
for 0 Hair Dryer Helmets = 0
The wattage for 2093.31
4-Slice Toasters = 0
0 watts are being calculated for
BTUh
The Total Outside Fresh Air CFM = 300
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 65615.385
The Total Tons of HVAC needed = 5.46794875