Project STARLIGHT BAPTIST UNITS 1 & 2 HVAC Calculations

Tue May 24 13:53:41 CDT 2005

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane Glass = 0
The Btuh Gain for 436.93 SqFt of East and West Double Pane Glass = 41508.35
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 807.76 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 1373.192
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 2 = 0
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 3 = 0
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 4 = 0

The Btuh Gain for 1426.30 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 6846.24

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 86 People = 860

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1426.30 SqFt of Area Lighting in an Office = 4278.9

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 1426.30 4-Slice Toasters = 0
0 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Reception Area Outside Fresh Air #4 = 1290 cfm
The Btuh Gain for Outside Fresh Air #4 = 38700
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 1290
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 93566.682

The Total Tons of HVAC needed = 7.7972235