Tue May 24 13:53:41 CDT 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane
Glass = 0
The Btuh Gain for 436.93 SqFt of East and West
Double Pane Glass = 41508.35
The Btuh Gain for 0 SqFt of
SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0
SqFt of South Single Pane Glass = 0
The Btuh Gain for 0
SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows
in Doors = 0
The Btuh Gain for 807.76 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 1373.192
The Btuh Gain for 0 SqFt of Mason Above
Grade No Insulation Wall Number 2 = 0
The Btuh Gain for 0 SqFt
of Mason Above Grade No Insulation Wall Number 3 = 0
The Btuh Gain
for 0 SqFt of Mason Above Grade No Insulation Wall Number 4 = 0
The Btuh Gain for 1426.30 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 6846.24
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 86 People = 860
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1426.30 SqFt of Area Lighting in an Office = 4278.9
The wattage for 0 Gallon Coffee Machines = 0
The wattage
for 0 SqFt of Electric Food Warmers = 0
The wattage for 0
SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of
Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry
Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage
for 0 Hair Dryer Helmets = 0
The wattage for 1426.30
4-Slice Toasters = 0
0 watts are being calculated for
BTUh
The Total Outside Fresh Air CFM = 1290
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 93566.682
The Total Tons of HVAC needed = 7.7972235