Church HVAC ProjectProject Church HVAC Calculations Mon Jan 29 12:36:30 CST 2007 There is no calculation for North & Shaded Glass There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 300 SqFt of East and West Single Pane Glass = 33000 There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 1020 SqFt of Mason Above Grade R-5 Wall Number 1 = 3162 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 2200 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 11440 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 70 People = 700 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 2200 SqFt of Area Lighting in an Office = 6600 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Cafeteria or Fast Food Outside Fresh Air #4 = 1400 cfm The Btuh Gain for Outside Fresh Air #4 = 42000 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 1400 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 96902 The Total Tons of HVAC needed = 8.07516666666667