Fri Aug 26 15:00:45 CDT 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
The Btuh Gain for 90
SqFt of East and West Single Pane Glass = 9900
There is no
calculation for SouthEast and SouthWest Glass
The Btuh Gain for 26
SqFt of South Single Pane Glass = 2080
There is no calculation
for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 360 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 936
The Btuh Gain for 480 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 2 = 1248
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 707 SqFt of Ceiling and Roof Combo No Insulation;
Ceiling Number 1 = 19796
The Btuh Gain for 821 SqFt of Roof
Only 5.25" - 6.5" R-19; Ceiling Number 2 = 19796
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 8 People = 80
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1528 SqFt of Area Lighting in an Office = 4584
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 630
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 61793.2
The Total Tons of HVAC needed = 5.14943333333333