Project PYTHON CONSTRUCTION- 2ND FLOOR HVAC Calculations

Tue May 17 12:25:12 CDT 2005

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane Glass = 0
The Btuh Gain for 50.00 SqFt of East and West Single Pane Glass = 5500
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 63.332 SqFt of South Single Pane Glass = 5066.56
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 64.00 SqFt of Windows in Doors = 844.8

The Btuh Gain for 747.50 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 1270.75
The Btuh Gain for 433.25 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 2 = 736.525
The Btuh Gain for 530.75 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 3 = 902.275
The Btuh Gain for 650.00 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 1105

The Btuh Gain for 2248.00 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 11689.6

The Btuh Gain for 0 SqFt of Roof Only No Insulation; Ceiling Number 2 = 11689.6

The Btuh Gain for 0 SqFt of Above Grade R-11 Floor Number 1 = 0
The Btuh Gain for 0 SqFt of Over Basement Floor Number 2 = 0

The Btuh Gain for 5 People = 50

The Btuh Gain for Motor 0 HP = 0

The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0

The Btuh Gain for 2248.00 SqFt of Area Lighting in an Office = 6744

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 2248.00 4-Slice Toasters = 0
0 watts are being calculated for BTUh

The Office Space Outside Fresh Air #1 = 314.72 cfm
The Btuh Gain for Outside Fresh Air #1 = 9441.6
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 314.72
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 43351.11

The Total Tons of HVAC needed = 3.6125925