Tue Mar 1 13:13:39 CST 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
The Btuh Gain for 81
SqFt of East and West Double Pane Glass = 7695
The Btuh Gain for
81 SqFt of SouthEast and SouthWest Double Pane Glass = 8100
The Btuh Gain for 277 SqFt of South Double Pane Glass = 19390
There is no calculation for SkyLights
There is no calculation for
Windows in Doors
The Btuh Gain for 135 SqFt of Wood R-11 & 1/2" Gypsum Wall Number
1 = 351
The Btuh Gain for 162 SqFt of Wood R-11 & 1/2"
Gypsum Wall Number 2 = 421.2
The Btuh Gain for 357 SqFt of
Wood R-11 & 1/2" Gypsum Wall Number 3 = 928.2
There is no
calculation for Wall Number 4
The Btuh Gain for 2608 SqFt of Roof Only 3" - 3.5" R-11; Ceiling
Number 1 = 21385.6
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 20 People = 200
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
There is no calculation for Lighting
The wattage for 2 Gallon Coffee Machines = 940
The wattage
for 20 SqFt of Electric Food Warmers = 2400
There is no
calculation for Gas Food Warmers
There is no calculation for Electric Fry
Kettle
There is no calculation for Gas Fry Kettle
There is no
calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
The wattage for
4-Slice Toasters = 2460
There is no calculation for other
appliances of known wattages
The Total Outside Fresh Air CFM = 400
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 90191
The Total Tons of HVAC needed = 7.51591666666667