Project South Seas Chinese Dining HVAC HVAC Calculations

Fri Dec 23 10:52:13 CST 2005

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 216 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 367.2
The Btuh Gain for 108 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 2 = 183.6
The Btuh Gain for 1185 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 3 = 2014.5
The Btuh Gain for 411 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 698.7

The Btuh Gain for 2537.14 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 12178.272

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

There is no calculation for People

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 2537.14 SqFt of Area Lighting in a Retail Store = 10148.56

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Dining Room Outside Fresh Air #1 = 3551.996 cfm
The Btuh Gain for Outside Fresh Air #1 = 106559.88
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 3551.996
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 132150.712

The Total Tons of HVAC needed = 11.0125593333333