Fri Dec 23 11:09:10 CST 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
There is no calculation for South Glass
There is no calculation
for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 795 SqFt of Wood R-19 & 1/2" Gypsum Wall Number
1 = 1351.5
The Btuh Gain for 348 SqFt of Wood R-19 & 1/2"
Gypsum Wall Number 2 = 591.6
The Btuh Gain for 793 SqFt of
Wood R-19 & 1/2" Gypsum Wall Number 3 = 1348.1
The Btuh Gain for
347 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 4 = 589.9
The Btuh Gain for 2160.64 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 10371.072
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
There is no calculation for People
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2160.64 SqFt of Area Lighting in a Retail Store = 8642.56
The wattage for 1 Gallon Coffee Machines = 470
There is no
calculation for Electric Food Warmers
The wattage for 15 SqFt of Gas
Food Warmers = 1800
There is no calculation for Electric Fry Kettle
The wattage for 10 SqFt of Gas Fry Kettle = 20000
There is
no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation
for 4-Slice Toaster
There is no calculation for other appliances of known
wattages
The Total Outside Fresh Air CFM = 648.192
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 118058.492
The Total Tons of HVAC needed = 9.83820766666667