Project China King HVAC Calculations

Tue Jun 29 12:01:14 EDT 2010

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
The Btuh Gain for 152 SqFt of SouthEast and SouthWest Single Pane Glass = 16720
There is no calculation for South Glass
There is no calculation for SkyLights
The Btuh Gain for 20 SqFt of Windows in Doors = 264

The Btuh Gain for 152 SqFt of Mason Above Grade R-5 Wall Number 1 = 471.2
The Btuh Gain for 1235 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 2 = 2840.5
The Btuh Gain for 1235 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 3 = 2840.5
The Btuh Gain for 152 SqFt of Mason Above Grade No Insulation Wall Number 4 = 1656.8

The Btuh Gain for 1268 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 6593.6

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 12 People = 120

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1268 SqFt of Area Lighting in an Office = 3804

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Dining Room Outside Fresh Air #1 = 560 cfm
The Btuh Gain for Outside Fresh Air #1 = 16800
The Kitchen Outside Fresh Air #2 = 260.4 cfm
The Btuh Gain for Outside Fresh Air #2 = 7812
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 820.4
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 59922.6

The Total Tons of HVAC needed = 4.99355