Project Quiznos 10143 Lafayette HVAC Calculations

Thu Feb 16 16:20:10 CST 2006

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
The Btuh Gain for 220 SqFt of SouthEast and SouthWest Double Pane Glass = 22000
There is no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 200 SqFt of Mason Above Grade No Insulation Wall Number 1 = 2180
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 1320 SqFt of Roof Only No Insulation; Ceiling Number 1 = 56760

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 25 People = 250

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1320 SqFt of Area Lighting in a Retail Store = 5280

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Cafeteria or Fast Food Outside Fresh Air #4 = 260 cfm
The Btuh Gain for Outside Fresh Air #4 = 7800
The Kitchen Outside Fresh Air #5 = 105 cfm
The Btuh Gain for Outside Fresh Air #5 = 3150
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 365
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 97420

The Total Tons of HVAC needed = 8.11833333333333