Project Quiznos 5989 Byram MS HVAC Calculations

Tue Feb 7 15:40:33 CST 2006

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
There is no calculation for SouthEast and SouthWest Glass
The Btuh Gain for 394 SqFt of South Single Pane Glass = 31520
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 394 SqFt of Mason Above Grade No Insulation Wall Number 1 = 4294.6
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 1990 SqFt of Roof Only No Insulation; Ceiling Number 1 = 85570

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 17 People = 170

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1990 SqFt of Area Lighting in a Retail Store = 7960

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Cafeteria or Fast Food Outside Fresh Air #4 = 480 cfm
The Btuh Gain for Outside Fresh Air #4 = 14400
The Kitchen Outside Fresh Air #5 = 135 cfm
The Btuh Gain for Outside Fresh Air #5 = 4050
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 615
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 147964.6

The Total Tons of HVAC needed = 12.3303833333333