Thu Jan 5 14:28:01 CST 2006
There is no calculation for North & Shaded Glass
The Btuh Gain for
542 SqFt of NorthEast and NorthWest Double Pane Glass = 37940
There is no calculation for East and West Glass
There is no
calculation for SouthEast and SouthWest Glass
There is no calculation for
South Glass
There is no calculation for SkyLights
There is no
calculation for Windows in Doors
The Btuh Gain for 100 SqFt of Mason Above Grade R-11 Wall Number 1 =
160
The Btuh Gain for 73 SqFt of Mason Above Grade R-11 Wall
Number 2 = 116.8
The Btuh Gain for 100 SqFt of Wood R-11 &
1/2" Gypsum Wall Number 3 = 260
The Btuh Gain for 20 SqFt of
Wood R-11 & 1/2" Gypsum Wall Number 4 = 52
The Btuh Gain for 7500 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 39000
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 121 People = 1210
The Btuh Gain for Motor 6 HP = 21000
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 7500 SqFt of Area Lighting in a Retail Store = 30000
The wattage for 4 Gallon Coffee Machines = 1880
There is no
calculation for Electric Food Warmers
There is no calculation for Gas Food
Warmers
There is no calculation for Electric Fry Kettle
There is no
calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
The wattage for 6 Hair
Dryer Helmets = 3900
There is no calculation for 4-Slice Toaster
20000 watts are being calculated as 68000 of BTUh
The Total Outside Fresh Air CFM = 1815
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 271840.8
The Total Tons of HVAC needed = 22.6534