HVAC ProjectProject Ashford Place Exercise Room HVAC Calculations Fri Feb 11 07:55:51 CST 2005 The Btuh Gain for 15 SqFt of North and Shaded Double Pane Glass = 300 There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 960 SqFt of East and West Double Pane Glass = 91200 The Btuh Gain for 120 SqFt of SouthEast and SouthWest Double Pane Glass = 12000 The Btuh Gain for 240 SqFt of South Triple Pane Glass = 13200 There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 408 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 1060.8 There is no calculation for Wall Number 2 The Btuh Gain for 312 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 3 = 811.2 The Btuh Gain for 264 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 4 = 686.4 The Btuh Gain for 1078 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 8839.6 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 31 People = 310 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 1078 SqFt of Area Lighting in an Office = 3234 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages The Office Space Outside Fresh Air #1 = 150.92 cfm The Btuh Gain for Outside Fresh Air #1 = 4527.6 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 There is no calculation for Outside Fresh Air #4 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 150.92 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 136169.6 The Total Tons of HVAC needed = 11.3474666666667