The Btuh Gain for 15 SqFt of North and Shaded Double Pane Glass =
300
The Btuh Gain for 45 SqFt of NorthEast and NorthWest
Double Pane Glass = 3150
There is no calculation for East and West
Glass
There is no calculation for SouthEast and SouthWest Glass
There is
no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 464 SqFt of Mason Above Grade R-11 Wall Number 1 =
742.4
The Btuh Gain for 256 SqFt of Mason Above Grade R-11
Wall Number 2 = 409.6
The Btuh Gain for 192 SqFt of Mason
Above Grade R-11 Wall Number 3 = 307.2
The Btuh Gain for 216
SqFt of Mason Above Grade R-11 Wall Number 4 = 345.6
The Btuh Gain for 1603 SqFt of Roof Only 3" - 3.5" R-11; Ceiling
Number 1 = 13144.6
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 106 People = 1060
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1603 SqFt of Area Lighting in an Office = 4809
The wattage for 1 Gallon Coffee Machines = 470
The wattage
for 2 SqFt of Electric Food Warmers = 240
There is no
calculation for Gas Food Warmers
The wattage for 2 SqFt of Electric
Fry Kettle = 2800
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for
Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no
calculation for 4-Slice Toaster
There is no calculation for other appliances
of known wattages
The Total Outside Fresh Air CFM = 1442.7
This is
in accordance with International Mechanical Code 2003
The Total BTUh Gain = 79483.4
The Total Tons of HVAC needed = 6.62361666666667