Tue May 24 14:36:04 CDT 2005
The Btuh Gain for 60.64 SqFt of North and Shaded Double Pane Glass =
1212.8
The Btuh Gain for 154.00 SqFt of NorthEast and
NorthWest Double Pane Glass = 10780
The Btuh Gain for 297.50
SqFt of East and West Double Pane Glass = 28262.5
The Btuh Gain
for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh
Gain for 0 SqFt of Windows in Doors = 0
The Btuh Gain for 534.75 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 909.075
The Btuh Gain for 637.33 SqFt of Wood R-19
& 1/2" Gypsum Wall Number 2 = 1083.461
The Btuh Gain for
377.58 SqFt of Wood No Insulation 1/2" Gypsum Wall Number 3 = 2945.124
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall
Number 4 = 0
The Btuh Gain for 1328.86 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 6378.528
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 9 People = 90
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1328.86 SqFt of Area Lighting in an Office = 3986.58
The wattage for 0 Gallon Coffee Machines = 0
The wattage
for 0 SqFt of Electric Food Warmers = 0
The wattage for 0
SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of
Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry
Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage
for 0 Hair Dryer Helmets = 0
The wattage for 1328.86
4-Slice Toasters = 0
0 watts are being calculated for
BTUh
The Total Outside Fresh Air CFM = 180
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 61048.068
The Total Tons of HVAC needed = 5.087339