Project STARLIGHT BAPTIST UNIT 9 NET HVAC Calculations

Thu Jun 9 12:54:17 CDT 2005

The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Double Pane Glass = 0
The Btuh Gain for 0 SqFt of East and West Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 534.75 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 909.075
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 2 = 0
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 3 = 0
The Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 4 = 0

The Btuh Gain for 2093 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 10046.4
The Btuh Gain for 0 SqFt of Roof Only No Insulation; Ceiling Number 2 = 10046.4

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 12 People = 120

The Btuh Gain for Motor 0 HP = 0

The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0

The Btuh Gain for 1851 SqFt of Area Lighting in an Office = 5553

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 1851 4-Slice Toasters = 0
0 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Dining Room Outside Fresh Air #4 = 240 cfm
The Btuh Gain for Outside Fresh Air #4 = 7200
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 240
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 23828.475

The Total Tons of HVAC needed = 1.98570625