Thu Jun 16 10:07:12 CDT 2005
The Btuh Gain for 0 SqFt of North and Shaded Single Pane Glass = 0
There is no calculation for NorthEast and NorthWest Glass
There is
no calculation for East and West Glass
The Btuh Gain for 72 SqFt of
SouthEast and SouthWest Double Pane Glass = 7200
There is no
calculation for South Glass
There is no calculation for SkyLights
There
is no calculation for Windows in Doors
The Btuh Gain for 340.20 SqFt of Mason Above Grade R-11 Wall Number 1
= 544.32
The Btuh Gain for 495.97 SqFt of Wood R-19 & 1/2"
Gypsum Wall Number 2 = 843.149
There is no calculation for Wall
Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 1659 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 7963.2
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 11 People = 110
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1436 SqFt of Area Lighting in an Office = 4308
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 220
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 27568.669
The Total Tons of HVAC needed = 2.29738908333333