Thu Jun 16 09:42:03 CDT 2005
The Btuh Gain for 120 SqFt of North and Shaded Double Pane Glass =
2400
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 210 SqFt of East and West Double Pane Glass =
19950
There is no calculation for SouthEast and SouthWest Glass
There is no calculation for South Glass
There is no calculation for
SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 233.969 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 397.7473
The Btuh Gain for 668.355 SqFt of Mason
Above Grade R-11 Wall Number 2 = 1069.368
There is no calculation for
Wall Number 3
There is no calculation for Wall Number 4
The Btuh Gain for 2140.0 SqFt of Ceiling and Roof Combo R-19; Ceiling
Number 1 = 10272
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 13 People = 130
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 2140.0 SqFt of Area Lighting in an Office = 6420
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 260
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 48439.1153
The Total Tons of HVAC needed = 4.03659294166667