HVAC ProjectProject Faith Bible Church HVAC Calculations Fri Feb 11 09:27:17 CST 2005 The Btuh Gain for 30 SqFt of North and Shaded Double Pane Glass = 600 There is no calculation for NorthEast and NorthWest Glass The Btuh Gain for 146 SqFt of East and West Double Pane Glass = 13870 There is no calculation for SouthEast and SouthWest Glass The Btuh Gain for 108 SqFt of South Double Pane Glass = 7560 There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 555 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 1 = 1443 The Btuh Gain for 660 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 2 = 1716 The Btuh Gain for 626 SqFt of Wood R-11 & 1/2" Gypsum Wall Number 3 = 1627.6 There is no calculation for Wall Number 4 The Btuh Gain for 3386 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 17607.2 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 200 People = 2000 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 3386 SqFt of Area Lighting in an Office = 10158 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages There is no calculation for Outside Fresh Air #1 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 The Reception Area Outside Fresh Air #4 = 3000 cfm The Btuh Gain for Outside Fresh Air #4 = 90000 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 3000 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 146581.8 The Total Tons of HVAC needed = 12.21515