Project PLATFORM CRANE SERVICE- 2ND FLOOR HVAC Calculations

Tue Apr 19 07:55:12 CST 2005

The Btuh Gain for 252.00 SqFt of North and Shaded Single Pane Glass = 7560
The Btuh Gain for 0 SqFt of NorthEast and NorthWest Single Pane Glass = 0
The Btuh Gain for 168 SqFt of East and West Single Pane Glass = 18480
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 0 SqFt of Windows in Doors = 0

The Btuh Gain for 856.21 SqFt of Mason Above Grade R-11 Wall Number 1 = 1369.936
The Btuh Gain for 321.13 SqFt of Mason Above Grade R-11 Wall Number 2 = 513.808
The Btuh Gain for 321.13 SqFt of Mason Above Grade R-11 Wall Number 3 = 513.808
The Btuh Gain for 1066 SqFt of Mason Above Grade R-5 Wall Number 4 = 3304.6

The Btuh Gain for 2241.70 SqFt of Roof Only 3" - 3.5" R-11; Ceiling Number 1 = 18381.94
The Btuh Gain for 0 SqFt of Roof Only No Insulation; Ceiling Number 2 = 18381.94

The Btuh Gain for 0 SqFt of Above Grade R-5 Floor Number 1 = 17261.09
There is no calculation for Floor Number 2

The Btuh Gain for 10 People = 100

The Btuh Gain for Motor 0 HP = 0

The Btuh Gain for 0 SqFt of Ducts Out of Conditioned Spaces = 0

The Btuh Gain for 2241.70 SqFt of Area Lighting in an Office = 6725.1

The wattage for 0 Gallon Coffee Machines = 0
The wattage for 0 SqFt of Electric Food Warmers = 0
The wattage for 0 SqFt of Gas Food Warmers = 0
The wattage for 0 SqFt of Electric Fry Kettle = 0
The wattage for 0 SqFt of Gas Fry Kettle = 0
The wattage for 0 SqFt of Electric Griddle = 0
The wattage for 0 SqFt of Gas Griddle = 0
The wattage for 0 Hair Dryer Helmets = 0
The wattage for 2241.70 4-Slice Toasters = 0
0 watts are being calculated for BTUh

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Office Space Outside Fresh Air #4 = 200 cfm
The Btuh Gain for Outside Fresh Air #4 = 6000
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 200
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 80210.282

The Total Tons of HVAC needed = 6.68419016666667