Parish Cab Co. HVAC ProjectProject Parish Cab Co. HVAC Calculations Tue Mar 6 13:46:15 CST 2007 The Btuh Gain for 75 SqFt of North and Shaded Double Pane Glass = 1500 There is no calculation for NorthEast and NorthWest Glass There is no calculation for East and West Glass There is no calculation for SouthEast and SouthWest Glass There is no calculation for South Glass There is no calculation for SkyLights There is no calculation for Windows in Doors The Btuh Gain for 1560 SqFt of Wood No Insulation 1/2" Gypsum Wall Number 1 = 12168 There is no calculation for Wall Number 2 There is no calculation for Wall Number 3 There is no calculation for Wall Number 4 The Btuh Gain for 1000 SqFt of Roof Only 2" - 2.5" R-7; Ceiling Number 1 = 11000 There is no calculation for Ceiling Number 2 There is no calculation for Floor Number 1 There is no calculation for Floor Number 2 The Btuh Gain for 7 People = 70 There is no calculation for Motor HP There is no calculation for Ducts Out of Conditioned Spaces The Btuh Gain for 1000 SqFt of Area Lighting in an Office = 3000 There is no calculation for Coffee Machines There is no calculation for Electric Food Warmers There is no calculation for Gas Food Warmers There is no calculation for Electric Fry Kettle There is no calculation for Gas Fry Kettle There is no calculation for Electric Griddle There is no calculation for Gas Griddle There is no calculation for Hair Dryer Helmets There is no calculation for 4-Slice Toaster There is no calculation for other appliances of known wattages The Office Space Outside Fresh Air #1 = 140 cfm The Btuh Gain for Outside Fresh Air #1 = 4200 There is no calculation for Outside Fresh Air #2 There is no calculation for Outside Fresh Air #3 There is no calculation for Outside Fresh Air #4 There is no calculation for Outside Fresh Air #5 There is no calculation for Outside Fresh Air #6 The Total Outside Fresh Air CFM = 140 This is in accordance with International Mechanical Code 2003 The Total BTUh Gain = 31938 The Total Tons of HVAC needed = 2.6615