Project Hollywood Nails HVAC Calculations

Mon Oct 27 13:57:55 EDT 2008

There is no calculation for North & Shaded Glass
There is no calculation for NorthEast and NorthWest Glass
There is no calculation for East and West Glass
The Btuh Gain for 184.5 SqFt of SouthEast and SouthWest Double Pane Glass = 18450
There is no calculation for South Glass
There is no calculation for SkyLights
There is no calculation for Windows in Doors

The Btuh Gain for 410 SqFt of Wood R-13 & 1/2" Gypsum Wall Number 1 = 943
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 1066 SqFt of Roof Only 8" - 9.5" R-30; Ceiling Number 1 = 3411.2

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

The Btuh Gain for 23.5 People = 235

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 1066 SqFt of Area Lighting in an Office = 3198

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

There is no calculation for Outside Fresh Air #1
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
The Office Space Outside Fresh Air #4 = 470 cfm
The Btuh Gain for Outside Fresh Air #4 = 14100
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 470
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 40337.2

The Total Tons of HVAC needed = 3.36143333333333