Wed May 25 08:25:00 CDT 2005
There is no calculation for North & Shaded Glass
There is no
calculation for NorthEast and NorthWest Glass
There is no calculation for
East and West Glass
There is no calculation for SouthEast and SouthWest
Glass
There is no calculation for South Glass
There is no calculation
for SkyLights
There is no calculation for Windows in Doors
The Btuh Gain for 400 SqFt of Wood No Insulation 1/2" Gypsum Wall
Number 1 = 3120
The Btuh Gain for 400 SqFt of Wood No
Insulation 1/2" Gypsum Wall Number 2 = 3120
The Btuh Gain for 400
SqFt of Wood No Insulation 1/2" Gypsum Wall Number 3 = 3120
The
Btuh Gain for 0 SqFt of Mason Above Grade No Insulation Wall Number 4 =
0
The Btuh Gain for 1600 SqFt of Roof Only 5.25" - 6.5" R-19; Ceiling Number 1 = 8320
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
The Btuh Gain for 40 People = 400
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 1600 SqFt of Area Lighting in an Office = 4800
The wattage for 2 Gallon Coffee Machines = 940
The wattage
for 2 SqFt of Electric Food Warmers = 240
There is no
calculation for Gas Food Warmers
There is no calculation for Electric Fry
Kettle
There is no calculation for Gas Fry Kettle
There is no
calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation
for 4-Slice Toaster
There is no calculation for other appliances of known
wattages
The Total Outside Fresh Air CFM = 800
This is in
accordance with International Mechanical Code 2003
The Total BTUh Gain = 50892
The Total Tons of HVAC needed = 4.241