Project La Quinta Biloxi Area 1 HVAC HVAC Calculations

Fri Nov 4 15:14:56 CST 2005

The Btuh Gain for 24.1666 SqFt of North and Shaded Double Pane Glass = 483.332
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 225.12377 SqFt of East and West Double Pane Glass = 21386.75815
The Btuh Gain for 0 SqFt of SouthEast and SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of SkyLights = 0
The Btuh Gain for 46.94294 SqFt of Windows in Doors = 619.646808

The Btuh Gain for 2258.4526 SqFt of Wood R-19 & 1/2" Gypsum Wall Number 1 = 3839.36942
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for Wall Number 4

The Btuh Gain for 5463.5656 SqFt of Ceiling and Roof Combo R-19; Ceiling Number 1 = 26225.11488

There is no calculation for Ceiling Number 2

There is no calculation for Floor Number 1
There is no calculation for Floor Number 2

There is no calculation for People

There is no calculation for Motor HP

There is no calculation for Ducts Out of Conditioned Spaces

The Btuh Gain for 5463.5656 SqFt of Area Lighting in an Office = 16390.6968

There is no calculation for Coffee Machines
There is no calculation for Electric Food Warmers
There is no calculation for Gas Food Warmers
There is no calculation for Electric Fry Kettle
There is no calculation for Gas Fry Kettle
There is no calculation for Electric Griddle
There is no calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for other appliances of known wattages

The Office Space Outside Fresh Air #1 = 764.899184 cfm
The Btuh Gain for Outside Fresh Air #1 = 22946.97552
There is no calculation for Outside Fresh Air #2
There is no calculation for Outside Fresh Air #3
There is no calculation for Outside Fresh Air #4
There is no calculation for Outside Fresh Air #5
There is no calculation for Outside Fresh Air #6

The Total Outside Fresh Air CFM = 764.899184
This is in accordance with International Mechanical Code 2003

The Total BTUh Gain = 91891.893578

The Total Tons of HVAC needed = 7.65765779816667