Fri Nov 4 15:14:56 CST 2005
The Btuh Gain for 24.1666 SqFt of North and Shaded Double Pane Glass =
483.332
There is no calculation for NorthEast and NorthWest Glass
The Btuh Gain for 225.12377 SqFt of East and West Double Pane Glass =
21386.75815
The Btuh Gain for 0 SqFt of SouthEast and
SouthWest Single Pane Glass = 0
The Btuh Gain for 0 SqFt of
South Single Pane Glass = 0
The Btuh Gain for 0 SqFt of
SkyLights = 0
The Btuh Gain for 46.94294 SqFt of Windows in
Doors = 619.646808
The Btuh Gain for 2258.4526 SqFt of Wood R-19 & 1/2" Gypsum Wall
Number 1 = 3839.36942
There is no calculation for Wall Number 2
There is no calculation for Wall Number 3
There is no calculation for
Wall Number 4
The Btuh Gain for 5463.5656 SqFt of Ceiling and Roof Combo R-19;
Ceiling Number 1 = 26225.11488
There is no calculation for Ceiling Number 2
There is no calculation for Floor Number 1
There is no calculation for
Floor Number 2
There is no calculation for People
There is no calculation for Motor HP
There is no calculation for Ducts Out of Conditioned Spaces
The Btuh Gain for 5463.5656 SqFt of Area Lighting in an Office = 16390.6968
There is no calculation for Coffee Machines
There is no calculation for
Electric Food Warmers
There is no calculation for Gas Food Warmers
There
is no calculation for Electric Fry Kettle
There is no calculation for Gas
Fry Kettle
There is no calculation for Electric Griddle
There is no
calculation for Gas Griddle
There is no calculation for Hair Dryer Helmets
There is no calculation for 4-Slice Toaster
There is no calculation for
other appliances of known wattages
The Total Outside Fresh Air CFM = 764.899184
This
is in accordance with International Mechanical Code 2003
The Total BTUh Gain = 91891.893578
The Total Tons of HVAC needed = 7.65765779816667